Small moors holiday park, Anchor Lane, Harvington, Evesham,
Electrical Inspection and tests
The site owner needed a Electrical test and inspection of the supply intakes to 98 caravans and all associated switch gear.
The supply intake was from a P.M.E. from a transformer
mounted on a Telegraph Pole in the main field
The Supply was 230V single phase 200 Amp on a 3 wire
system Earth Neutral combined at the intake.
The Out going supply circuit were protect by a 2 off 300mA time delay RCD unit.
Caravans on site with P.M.E. supplies should not be connected
to the earth of the intake so the owner had install earth rods to all the pitches. We modifyed the earth arrangement to the earth eletrode and performed the following tests on all 98 Caravan supply boxes as shown in the picture.
Earth Electrode Test
RCD test on the 30mA RCD in the supply box
Function testing of RCD and MCB
We also tested all the supply boards and switch gear for the caravan circuits
All the work work was certified and registered for Part P